Bus Fault


 
How to locate and repair a DALI Bus Fault 




When you enter scan for devices - if you get a DALI Bus Fault - then you have either:

a) a short on the DALI bus in one of the devices

b) a failed DALI power supply



The DALI bus is powered by the Hub.    There are two power levels, 80 mA and 240 mA

80 mA is fine for most projects - if there are more than 40 DALI devices, then 240 mA is needed

Visit  Advanced
Click on DALI Bus Power status
the voltage should be over 14 volts, with the current less than 260 mA


Visit Logs

The DALI bus status is reported in real time as follows  ( x can be 1 to 4 )

D0x  no power or short
D1x  bus shorted to 12v or similar
D2x  bus OK
D3x  bus not tested yet
D4x  bus shorted to 24 volts or higher



Locatiing:

Unplug all PSE devices except one

Activate one PSE at a time to see if the bus returns to D2x status

unplug all loads, insert until one load causes the problem.